-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24110910
Plan Review Stops For Permit 24110910
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 01-16-2025 Cont ID  
Sent By cdorman Date 01-16-2025 Time 15:02 Rev Time 0.00
Received By cdorman Date 01-07-2025 Time 09:46 Sent To  
Notes
2025-01-07 09:46:38.00000PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 12-18-2024 Cont ID  
Sent By cdorman Date 12-18-2024 Time 14:12 Rev Time 0.00
Received By cdorman Date 12-18-2024 Time 09:02 Sent To  
Notes
2024-12-18 14:12:29.00000SHEET E-01:
 PROTECT THE EXISTING INTERIOR PANEL AND THE FEEDERS
 SUPPLYING IT AT NO MORE THAN 150A OR REPLACE FEEDER
 CONDUCTORS AND INTERIOR PANEL WITH 200A RATED (IN THIS
 CASE PROTECTED BY 200A ATS BRKR).
 EXISTING FEEDER CONDUCTORS AND INTERIOR PANEL ARE RATED
 FOR 150A AND ARE PROPOSED TO BE SUPPLIED BY BOTH
 UTILITY AND PV SOURCES WITH A COMBINED INPUT EXCEEDING
 150A.
 SEE 705.12 (B)(1) & (2)
2024-12-18 09:02:59.00000PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 12-11-2024 Cont ID  
Sent By cdorman Date 12-11-2024 Time 14:14 Rev Time 0.00
Received By cdorman Date 11-27-2024 Time 11:57 Sent To  
Notes
2024-12-13 09:18:50.00000SENT REQUEST FOR PAYMENT
2024-11-27 11:57:49.00000PERMITS@SUNVENA.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved