Plan Review Details - Permit 24100734
Plan Review Stops For Permit 24100734
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 11-27-2024 Cont ID  
Sent By cdorman Date 11-27-2024 Time 14:15 Rev Time 0.00
Received By cdorman Date 11-21-2024 Time 14:04 Sent To  
Notes
2024-12-05 11:15:35.00000SENT REQUEST FOR PAYMENT
2024-11-21 14:05:13.00000LISACERROSORANTES@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status R Date 11-13-2024 Cont ID  
Sent By cdorman Date 11-13-2024 Time 08:38 Rev Time 0.00
Received By cdorman Date 11-12-2024 Time 09:52 Sent To  
Notes
2024-11-13 08:38:46.00000SHEET PV4: NO CHANGE TO INITIAL PLANS. NOTE INDICATES
 THAT THE 7.6 KW STRING INVERTER OUTPUT WILL BE
 PCS-CONTROLLED WITH A CURRENT OUTPUT SETTING OF 120A.
 SHOW PCS BUS OR SERVICE CONDUCTOR MONITORING
 SYSTEM/COMPONENTS THIS PLAN SHEET. SHOW PERMANENT LABEL
 INDICATING THE OUTPUT PARAMETERS OF THE PCS.
2024-11-12 09:52:40.00000PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-28-2024 Cont ID  
Sent By cdorman Date 10-28-2024 Time 16:05 Rev Time 0.00
Received By cdorman Date 10-25-2024 Time 15:59 Sent To  
Notes
2024-10-28 16:05:47.00000SHEET PV-4: 125% OF INVERTER OUTPUT PLUS MAIN BREAKER
 RATING EXCEEDS 120% OF THE BUSBAR. (32 X 1.25) + 150 >
 150 X 1.20
 SEE NEC 705.12 (B)(3)(2).