Plan Review Details - Permit 24100091
Plan Review Stops For Permit 24100091
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 12-11-2024 Cont ID  
Sent By cdorman Date 12-11-2024 Time 14:14 Rev Time 0.00
Received By cdorman Date 11-27-2024 Time 12:31 Sent To  
Notes
2024-11-27 12:31:50.00000PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-23-2024 Cont ID  
Sent By cdorman Date 10-23-2024 Time 12:41 Rev Time 0.00
Received By cdorman Date 10-14-2024 Time 13:28 Sent To  
Notes
2024-10-28 12:05:24.00000EMAILED FEE OWED 10/28
2024-10-28 12:04:37.00000OR BK 3075 PG 1045
2024-10-14 13:28:33.00000REVISION SENT IN PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-02-2024 Cont ID  
Sent By cdorman Date 10-02-2024 Time 16:36 Rev Time 0.00
Received By cdorman Date 10-02-2024 Time 15:35 Sent To  
Notes
2024-10-02 16:36:36.00000SHEET PV4:
 1] SHOW CONDUCTOR SIZE BETWEEN COMBINER PANEL AND PV
 DISCONNECT
 2] CLEARLY INDICATE METHOD OF INTERCONNECTION. A 70A
 BACKFED BREAKER IS INDICATED; HOWEVER, A LINE SIDE TAP
 IS DRAWN. THE BACKFED BREAKER OPTION WILL NOT BE
 APPROVED DUE TO TOTAL SYSTEM OUTPUT AND EXISTING PANEL
 RATING.
 3] REMOVE BACKFEED FUSE SIZING TABLE FROM TOP LEFT
 CORNER OF SHEET.
  
 SHEET PV7: SHOW CORRECT CURRENT VALUE IN AC LABEL
  
2024-10-02 15:35:37.00000PERMITSARASOTA@FREEDOMFOREVER.COM