-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24090538
Plan Review Stops For Permit 24090538
Review Stop ADDRESSING ADDRESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 09-18-2024 Time 10:32 Sent To  
Notes
***NONE***

Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 02-21-2025 Time 14:15 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-01-2024 Cont ID  
Sent By cdorman Date 10-01-2024 Time 14:48 Rev Time 0.00
Received By cdorman Date 10-01-2024 Time 13:35 Sent To  
Notes
2024-10-01 13:35:25.00000REVISED PLANS SHERYL.DENAN@SMARTLINKGROUP.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 09-18-2024 Cont ID  
Sent By cdorman Date 09-18-2024 Time 14:48 Rev Time 0.00
Received By cdorman Date 09-18-2024 Time 10:32 Sent To  
Notes
2024-09-18 14:48:09.00000PLANS MUST BE COMPLIANT WITH 8TH EDITION FLORIDA
 BUILDING CODE AND 2020 NATIONAL ELECTRICAL CODE.
 COMPLIANCE CERTIFICATION MUST APPEAR ON SHEET T-1
 (CURRENTLY SHOWS COMPLIANCE WITH A PREVIOUS CODE
 EDITION).
 ALTERNATIVELY, WILL ACCEPT ENGINEER'S LETTER
 REFERENCING PLANS AND ATTESTING TO COMPLIANCE AS
 REQUIRED.
  
 SHEET E-5: CHANGE UNGROUNDED CONDUCTORS BETWEEN 175A
 GENERATOR BREAKER AND ATS TO MINIMUM 2/0 CU.
2024-09-18 10:38:53.00000SHERYL.DENAN@SMARTLINKGROUP.COM

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ZONING ZONING DEPARTMENT
Rev No 1 Status A Date 09-18-2024 Cont ID  
Sent By cshackel Date 09-18-2024 Time 10:32 Rev Time 0.00
Received By cshackel Date 09-18-2024 Time 10:32 Sent To  
Notes
***NONE***

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved