Review Stop BUILDING BUILDING DEPARTMENT
Rev No 10 Status A Date 06-25-2025 Cont ID  
Sent By cdorman Date 06-25-2025 Time 16:09 Rev Time 0.00
Received By cdorman Date 06-19-2025 Time 09:19 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 9 Status A Date 05-20-2025 Cont ID  
Sent By cdorman Date 05-20-2025 Time 14:34 Rev Time 0.00
Received By cdorman Date 05-12-2025 Time 12:55 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 8 Status R Date 05-06-2025 Cont ID  
Sent By cdorman Date 05-06-2025 Time 15:15 Rev Time 0.00
Received By cdorman Date 05-02-2025 Time 09:00 Sent To  
Notes
2025-05-06 15:15:41.00000PROVIDE REVISED PLANS; ONLY REC'D ENGINEER'S
 LETTER/CALCS.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 7 Status A Date 04-10-2025 Cont ID  
Sent By cdorman Date 04-10-2025 Time 16:09 Rev Time 0.00
Received By cdorman Date 04-02-2025 Time 13:11 Sent To  
Notes
2025-04-02 13:11:22.00000REVISED PLAN PANEL LAYOUT CHANGE JAIMIE@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 03-12-2025 Time 12:57 Sent To  
Notes
2025-03-12 12:57:34.00000REVISED PLANS MELAINA@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status D Date 03-06-2025 Cont ID  
Sent By cdorman Date 03-06-2025 Time 15:04 Rev Time 0.00
Received By cdorman Date 03-06-2025 Time 07:45 Sent To  
Notes
2025-03-06 15:04:42.00000SHEET PV-6: RELOCATE PV FEEDER TAP INTERCONNECTION TO
 LOAD SIDE OF NEW 100A HOUSE DISCONNECT. THE CONCERN IS
 OVERLOADING THE BUS OF THE 150A METER-MAIN (IF ANY
 BRANCH OR FEEDER BREAKERS ARE INSTALLED) WHEN SUPPLIED
 BY BOTH UTILITY AND PV INPUTS [150 + (30.25 X 1.25)] >
 150 X 1.20.
 SEE 705.12 (B).
2025-03-06 07:45:54.00000REVISION MELAINA@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 11-21-2024 Cont ID  
Sent By cdorman Date 11-21-2024 Time 07:59 Rev Time 0.00
Received By cdorman Date 11-08-2024 Time 10:12 Sent To  
Notes
2024-11-08 10:13:20.00000SUBMITTED REVISED PLANS 11-8-24 MELAINA@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 10-02-2024 Cont ID  
Sent By cdorman Date 10-02-2024 Time 13:55 Rev Time 0.00
Received By cdorman Date 09-20-2024 Time 09:46 Sent To  
Notes
2024-10-04 08:33:25.00000SENT REVISED PLANS 10/04
  
2024-09-20 09:47:16.00000REVISED PLAN SUBMITTED AGAIN... MELAINA@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cdorman Date 09-11-2024 Time 14:41 Sent To  
Notes
2024-09-11 14:42:22.00000CONTRACTOR'S EC LICENSE NUMBER REFERENCED ON
 APPLICATION. NO ADDITIONAL PLAN REVIEW FEE.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status R Date 09-04-2024 Cont ID  
Sent By cdorman Date 09-04-2024 Time 13:38 Rev Time 0.00
Received By cdorman Date 09-04-2024 Time 13:03 Sent To  
Notes
2024-09-13 16:16:01.00000SENT PAYMENT REQ
2024-09-09 13:09:19.00000NOC IS IN ONBASE 9/9/24 OR BK 3067 PG 209
2024-09-04 13:38:19.00000SCOPE OF WORK INCLUDES SERVICE ALTERATION; CONTRACTOR
 IS CVC; A SEPARATE ELECTRICAL PERMIT IS REQUIRED FROM A
 LICENSED EC (OR PRIME CONTRACTOR MAY USE ELECTRICAL
 LICENSE ON APPLICATION IF HE HAS THAT QUALIFICATION)
2024-09-04 13:03:50.00000MELAINA@LUNEXPOWER.COM