Plan Review Details - Permit 24080526
Plan Review Stops For Permit 24080526
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 09-24-2024 Cont ID  
Sent By cdorman Date 09-24-2024 Time 14:22 Rev Time 0.00
Received By cdorman Date 09-20-2024 Time 13:38 Sent To  
Notes
2024-09-25 09:03:15.00000SENT EXAMINER COMMENTS 09/25 TO PERMITS SARASOTA
2024-09-24 14:22:29.00000SHEET PV4:
 1] IN NEW COMBINER PANEL, SHOW 30A OVERCURRENT
 PROTECTION FOR EXISTING SYSTEM (BASED ON 5 KW EXISTING
 SYSTEM INVERTER).
 2] SHOW CONDUCTOR SIZES BETWEEN EXISTING SYSTEM
 INVERTER AND NEW COMBINER PANEL.
 3] SHOW CONDUCTOR SIZES BETWEEN NEW COMBINER PANEL AND
 NEW PV DISCONNECT.
2024-09-20 13:39:14.00000EMAILED IN FROM LISACERROSORANTES@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-20-2024 Cont ID  
Sent By cdorman Date 08-20-2024 Time 14:29 Rev Time 0.00
Received By cdorman Date 08-19-2024 Time 10:23 Sent To  
Notes
2024-08-26 09:10:32.00000NOC IN ON BASE. OR BK 3063 PG 1914
  
2024-08-20 14:29:35.00000SHEET PV4 (ONE-LINE): CONDUCTORS BETWEEN SUPPLY-SIDE
 TAP AND PV DISCONNECT MUST BE MINIMUM #6 CU; CONDUCTORS
 BETWEEN PV DISCONNECT AND SOLAR LOAD CENTER DO NOT HAVE
 SUFFICIENT AMPACITY FOR THE PROPOSED 60A OCPD. CHANGE
 CONDUCTOR SIZES AND/OR FUSES TO COMPLY WITH 705.11 (B)
 AND TBL. 310.16.
 RIGHT SIDEBAR (AND POSSIBLY AFFECTING DATA ON OTHER
 SHEETS): EXISING PV SYSTEM IS SHOWN INCORPORATING A
 .026 KW INVERTER. PLEASE VERIFY THE EXISTING EQUIPMENT.
2024-08-19 10:23:56.00000PERMITS SARASOTA