Plan Review Details - Permit 24070696
Plan Review Stops For Permit 24070696
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-31-2024 Cont ID  
Sent By cdorman Date 07-31-2024 Time 14:29 Rev Time 0.00
Received By cdorman Date 07-31-2024 Time 14:29 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-23-2024 Cont ID  
Sent By cdorman Date 07-23-2024 Time 15:14 Rev Time 0.00
Received By cdorman Date 07-23-2024 Time 13:17 Sent To  
Notes
2024-07-23 15:14:28.00000SHEETS S-1 & E-1:
 1] A READILY ACCESSIBLE RAPID SHUTDOWN INITIATION
 DEVICE SHALL BE LOCATED ON THE EXTERIOR OF THE HOUSE
 PER 690.12 (C). AN EXTERIOR SERVICE DISCONNECT WILL
 SATISFY THIS REQUIREMENT IF IT IS LABELED PER 690.56
 (C).
 2] A READILY ACCCESSIBLE AND PERMANENTLY IDENTIFIED ESS
 DISCONNECT SWITCH OR ITS REMOTE CONTROL DEVICE MUST BE
 INSTALLED ON THE EXTERIOR OF THE HOUSE PER 706.15 (A).
 BOTH OF THESE FUNCTIONS MAY BE ACCOMPLISHED BY A SINGLE
 REMOTE CONTROL DEVICE WHICH DISABLES ALL OUTPUT CURRENT
 FROM THE INVERTER. SUCH A DEVICE MUST BE LOCATED ON THE
 EXTERIOR OF THE BUILDING AND MUST BE CLEARLY IDENTIFIED
 AS TO ITS PURPOSE.
2024-07-23 13:17:28.00000IN OFFICE APP
  