-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24060283
Plan Review Stops For Permit 24060283
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status A Date 09-25-2024 Cont ID  
Sent By cdorman Date 09-25-2024 Time 12:24 Rev Time 0.00
Received By cdorman Date 09-17-2024 Time 08:40 Sent To  
Notes
2024-09-17 08:40:48.00000REVISION SENT IN VIA EMAIL FROM
 PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status D Date 08-28-2024 Cont ID  
Sent By cdorman Date 08-28-2024 Time 15:33 Rev Time 0.00
Received By cdorman Date 08-28-2024 Time 14:21 Sent To  
Notes
2024-08-28 15:33:21.00000RE-WORK SHEET PV4. TEXT IS OVERLAPPING IN AT LEAST FOUR
 LOCATIONS, OVERCURRENT PROTECTION DOES NOT CORRESPOND
 WITH CONDUCTOR SIZES IN ALL LOCATIONS. ALL TEXT AND
 DIAGRAMS ON SHEET MUST BE CLEAR, ACCURATE, AND LEGIBLE,
 AND MUST INCLUDE THE FOLLOWING:
 1] SHOW ALL CONDUCTOR SIZES AND OVERCURRENT RATINGS
 2] SHOW EXISTING SYSTEM MICROINVERTER TYPE AND RATING
 3] SHOW QUANTITY OF EXISTING MODULES CONNECTED VIA
 LINE-SIDE TAP AND QUANTITY OF EXISTING MODULES COMBINED
 WITH NEW PROPOSED SYSTEM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 07-31-2024 Cont ID  
Sent By cdorman Date 07-31-2024 Time 14:49 Rev Time 0.00
Received By cdorman Date 07-22-2024 Time 11:54 Sent To  
Notes
2024-07-22 11:55:27.00000REVISIONS PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-26-2024 Cont ID  
Sent By cdorman Date 06-26-2024 Time 13:40 Rev Time 0.00
Received By cdorman Date 06-19-2024 Time 13:41 Sent To  
Notes
2024-06-28 08:08:53.00000SENT PAYMENT REQ
  
2024-06-19 13:42:07.00000REQUESTED CORRECTIONS SUBMITTED
 PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-12-2024 Cont ID  
Sent By cdorman Date 06-12-2024 Time 14:15 Rev Time 0.00
Received By cdorman Date 06-10-2024 Time 15:34 Sent To  
Notes
2024-06-12 14:15:08.00000SHEET PV2: TESLA GATEWAY AND POWERWALL ARE SHOWN INSIDE
 THE GARAGE. PROVIDE A PERMANENTLY LABELED AND READILY
 ACCESSIBLE DISCONNECTING MEANS FOR THE POWERWALL ON THE
 EXTERIOR OF THE HOUSE, 706.15 (A). THIS MAY BE
 ACCOMPLISHED BY INSTALLING A REMOTE E-STOP DEVICE
 CONTROLLING THE GATEWAY NON-UTILITY OUTPUT.
 SHEET PV4: INDICATE THE LOCATION OF THE ABOVE
 DISCONNECTING MEANS ON THE ONE-LINE DIAGRAM.
 SHEET PV7: SHOW THE AC CURRENT/VOLTAGE LABEL WITH BOTH
 PARAMETERS FILLED IN
 SHEET PV7: SHOW THE LABEL IDENTIFYING THE ENERGY
 STORAGE SYSTEM DISCONNECTING MEANS
  
2024-06-10 15:35:23.00000PERMITSARASOTA@FREEDOMFOREVER.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved