-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24060283
Plan Review Stops For Permit 24060283
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-26-2024 Cont ID  
Sent By cdorman Date 06-26-2024 Time 13:40 Rev Time 0.00
Received By cdorman Date 06-19-2024 Time 13:41 Sent To  
Notes
2024-06-28 08:08:53.00000SENT PAYMENT REQ
  
2024-06-19 13:42:07.00000REQUESTED CORRECTIONS SUBMITTED
 PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-12-2024 Cont ID  
Sent By cdorman Date 06-12-2024 Time 14:15 Rev Time 0.00
Received By cdorman Date 06-10-2024 Time 15:34 Sent To  
Notes
2024-06-12 14:15:08.00000SHEET PV2: TESLA GATEWAY AND POWERWALL ARE SHOWN INSIDE
 THE GARAGE. PROVIDE A PERMANENTLY LABELED AND READILY
 ACCESSIBLE DISCONNECTING MEANS FOR THE POWERWALL ON THE
 EXTERIOR OF THE HOUSE, 706.15 (A). THIS MAY BE
 ACCOMPLISHED BY INSTALLING A REMOTE E-STOP DEVICE
 CONTROLLING THE GATEWAY NON-UTILITY OUTPUT.
 SHEET PV4: INDICATE THE LOCATION OF THE ABOVE
 DISCONNECTING MEANS ON THE ONE-LINE DIAGRAM.
 SHEET PV7: SHOW THE AC CURRENT/VOLTAGE LABEL WITH BOTH
 PARAMETERS FILLED IN
 SHEET PV7: SHOW THE LABEL IDENTIFYING THE ENERGY
 STORAGE SYSTEM DISCONNECTING MEANS
  
2024-06-10 15:35:23.00000PERMITSARASOTA@FREEDOMFOREVER.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved