Plan Review Stops For Permit 24050924
Review Stop AVONPARK AVON PARK CITY - FDO
Rev No 1 Status X Date 05-31-2024 Cont ID  
Sent By cshackel Date 05-31-2024 Time 10:09 Rev Time 0.00
Received By cshackel Date 05-31-2024 Time 10:09 Sent To  
Notes
2024-05-31 10:10:19.00000PER RANDY LABELLE NOTHING REQUIRED FROM THE CITY OF
 AVON PARK BECAUSE NO CHANGE IN FOOTPRINT AND ITS THE
 SAME USAGE.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-04-2024 Cont ID  
Sent By shullett Date 09-04-2024 Time 15:31 Rev Time 0.00
Received By shullett Date 09-04-2024 Time 08:30 Sent To  
Notes
2024-09-04 15:31:47.00000APPROVED PER CHUCK & ERIC
2024-09-04 15:30:56.00000RECEIVED VIA EMAIL A RESPONSE LETTER AND REVISED PLANS;
 FORWARDED TO CHUCK, JOHN & ERIC

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status R Date 07-22-2024 Cont ID  
Sent By hlopez Date 07-22-2024 Time 15:57 Rev Time 0.00
Received By hlopez Date 05-31-2024 Time 10:10 Sent To  
Notes
2024-07-22 15:57:48.00000JOHN AND I IDENTIFIED THE FOLLOWING POSSIBLE ELECTRICAL
 ISSUES WITH THE PLANS YOU SENT, ALL ON SHEET E401-B:
  
 1] CHANGE CIRCUIT BREAKER SUPPLYING RTU-1 TO A 300 AMP
 TO COMPLY WITH MAXIMUM OVERCURRENT RATING LISTED ON
 SHEET H001 FOR THIS UNIT.
  
 2] REVISIT FEEDER SCHEDULE: CIRCUIT IDENTIFIER “E”
 APPEARS TWICE IN THE LIST AND IS NOT SHOWN IN ANY
 CALLOUT ON THE SHEET.
  
 3] IN THE RISER DIAGRAM, PANEL “R1” APPEARS TWICE;
 FEEDER CALLOUT “F” (#12 AWG) IS INCORRECT FOR THESE
 CONDUCTOR SIZES PROTECTED BY A 250A OCPD.
  
 4] INSERT NOTE FOR CONTRACTOR TO VERIFY HORSEPOWER
 RATING OF NEW BALER: 150A CIRCUIT BREAKER SUPPLYING #2
 AWG CONDUCTORS MUST COMPLY WITH 430.22 FOR MOTOR
 CIRCUIT CONDUCTORS AND WITH TBL. 430.52 FOR MOTOR
 GROUND-FAULT SHORT-CIRCUIT PROTECTION.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date   Cont ID  
Sent By   Date 07-02-2024 Time 11:22 Rev Time 0.00
Received By cshackel Date 05-31-2024 Time 10:10 Sent To  
Notes
2024-07-22 16:01:09.00000MAKE SURE THE FDC CONNECTION IN THE REAR OF THE
 BUILDING IS PROPERLY CAPPED. NFPA STATES THEY NEED TO
 BE PROPERLY COVERED SO NO FOREIGN OBJECT CAN GET IN AND
 RESTRICT WATER FLOW.
2024-06-07 12:26:03.00000RECEIVED $79.00 CK #12035 PAYABLE TO CITY OF AVON PARK,
 GIVEN TO ERIC