-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24050658
Plan Review Stops For Permit 24050658
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 06-28-2024 Cont ID  
Sent By cdorman Date 06-28-2024 Time 13:12 Rev Time 0.00
Received By cdorman Date 06-27-2024 Time 15:03 Sent To  
Notes
2024-06-28 13:12:19.00000SHEET PV6:
 1] SHOW INTERCONNECTION AS "FEEDER TAP", NOT "SUPPLY
 SIDE CONNECTION"
 2] ADD #6 CU EQUIPMENT GROUNDING CONDUCTOR TO FEEDER
 TAP BETWEEN PV DISCONNECT AND ATS (CONDUCTOR ID #4).
2024-06-27 15:03:44.00000MELAINA@LUNEXPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 06-05-2024 Cont ID  
Sent By cdorman Date 06-05-2024 Time 14:03 Rev Time 0.00
Received By cdorman Date 05-21-2024 Time 15:19 Sent To  
Notes
2024-05-28 13:26:27.00000NOC IS IN ONBASE OR BK 3045 PG 1919
2024-05-21 15:19:58.00000MELAINA@LUNEXPOWER.COM