Plan Review Details - Permit 24050361
Plan Review Stops For Permit 24050361
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 05-15-2024 Cont ID  
Sent By cdorman Date 05-15-2024 Time 15:39 Rev Time 0.00
Received By cdorman Date 05-13-2024 Time 12:51 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By elthomps Date 05-10-2024 Time 14:12 Sent To  
Notes
2024-05-13 12:51:02.00000RECIEVED REVISION VIA WALK-IN
  
2024-05-10 15:49:29.00000SHEET PV-2 & PV-3: PROVIDE A READILY ACCESSIBLE RAPID
 SHUTDOWN INITIATION DEVICE ON THE EXTERIOR OF THE
 STRUCTURE PER 690.12 (C) (1). RAPID SHUTDOWN SHALL
 OCCUR BY THE OPERATION OF A SINGLE DEVICE, SUCH AS A PV
 DISCONNECT. THE USE OF MULTIPLE CIRCUIT BREAKERS IN A
 COMBINER PANEL IS NOT APPROVED FOR RAPID SHUTDOWN
 INITIATION.
2024-05-10 14:12:32.00000IN OFFICE *