Plan Review Details - Permit 24040187
Plan Review Stops For Permit 24040187
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-09-2025 Cont ID  
Sent By elongsho Date 05-06-2025 Time 21:20 Rev Time 0.00
Received By hlopez Date 04-24-2025 Time 13:55 Sent To  
Notes
2025-06-13 12:59:32.00000PER CAROL ALL PAPERWORK GIVEN BACK TO CONTRACTOR BUT
 HAS ALREADY BEEN SCANNED INTO ONBASE
2025-05-06 21:21:02.00000PREVIOUS NOTES NOT ADDRESSED.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-22-2024 Cont ID  
Sent By cshackel Date 05-22-2024 Time 10:12 Rev Time 0.00
Received By trowe Date 04-24-2025 Time 13:54 Sent To  
Notes
2024-05-22 10:13:02.00000PLANS ARE INCOMPLETE. THE FOLLOWING ADDITIONS WILL NEED
 TO BE MADE AND PLANS RESUBMITTED FOR
 REVIEW.
 1. THERE ARE NO MECHANICAL PAGES. MECHANICAL PAGES WILL
 NEED TO BE ADDED.
 2. THE PLUMBING PLAN IS INCOMPLETE. PLUMBING PAGES MUST
 INCLUDE DRAINAGE DETAILS,
 SUPPLY DETAILS, GREASE TRAP DETAILS, ADA DETAILS, FLOOR
 DRAIN DETAILS, CHECK VALVES FOR ICE
 MACHINE AND BEVERAGE DISPENSER, WATER HEATER DETAILS,
 GAS LINES, CO2 LINES, FILTERS??ETC.
 3. THE ELECTRICAL PAGES ARE INCOMPLETE. THIS PROJECT
 WILL REQUIRE A LOAD CALCULATION. PLANS
 NEED TO INCLUDE A PANEL SCHEDULE AND RISER DIAGRAM.
 4. PLANS NEED TO INCLUDE NOTES TO INCLUDE (BUT NOT
 LIMITED TO) USE AND OCCUPANCY
 CLASSIFICATION, CONSTRUCTION TYPE, OCCUPANCY LOAD, FIRE
 CODE REFERENCE, ADDRESS SIZE AND
 LOCATION, KNOX BOX??(CHECK WITH FIRE MARSHAL), ETC.
 5. LIFE SAFETY PAGE IS INCOMPLETE, SEE FIRE MARSHAL
 NOTES.
 SINCERELY,
 ERIC R.

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status C Date 06-13-2025 Cont ID  
Sent By hlopez Date 06-05-2025 Time 12:35 Rev Time 0.00
Received By hlopez Date 04-04-2024 Time 11:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status A Date 07-09-2025 Cont ID  
Sent By hlopez Date 07-09-2025 Time 15:28 Rev Time 0.00
Received By hlopez Date 07-01-2025 Time 15:17 Sent To  
Notes
2025-07-09 15:28:25.00000PLAN REVIEW #: 24040187
 PROJECT: SMOKE SHACK – BUILDING
 LOCATION: 123 US 27 N, LAKE PLACID
 OCCUPANCY: ASSEMBLY
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 7/9/2025
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED WITH COMMENTS
 ADD EMERGENCY LIGHT IN SMOKE ROOM AS SHOWN ON PLAN
 REVIEW FEE – $400 + INSPECTION FEE - $50 = $450
 ...

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status A Date   Cont ID  
Sent By   Date 05-06-2025 Time   Rev Time 0.00
Received By   Date 04-20-2025 Time   Sent To  
Notes
2025-05-06 10:29:30.00000PLAN REVIEW #: 24040187
 PROJECT: SMOKE SHACK – BUILDING
 LOCATION: 123 US 27 N, LAKE PLACID
 OCCUPANCY: ASSEMBLY
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/6/2025
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED WITH COMMENTS
 ITEMS ADDED ON PLANS:
  TRAVEL, DEAD END, COMMON PATH DISTANCES NEED
 ON PLANS ADDED TO THE PLANS.
  ELECTRICAL PANELS WILL REQUIRE BREAKERS TO BE
 LABELED FOR EXIT/EMERGENCY LIGHTS.
 SHALL SUBMIT SEPARATE PLANS FOR THE SPRINKLER SYSTEM,
 FIRE ALARM SYSTEM, KITCHEN HOOD SYSTEM,
 HOOD EXTINGUISHER SYSTEM, AND ALARM SYSTEM.
 REVIEW FEE – $400 + INSPECTION FEE - $50 = $450

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status D Date 05-20-2024 Cont ID  
Sent By cshackel Date 05-20-2024 Time 15:02 Rev Time 0.00
Received By cshackel Date 04-04-2024 Time 11:28 Sent To  
Notes
2024-05-20 15:02:19.00000CORRECTYIONS TO PLANS ARE NEEDED.
 • EXTINGUISHERS ONE AT FRONT EXIT, ONE AT REAR EXIT AT
 BATHROOMS, AND ONE IN KITCHEN NEAR SMOKE ROOM
 • EXIT SIGN NEEDED AT KITCHEN DOOR LEADING TO BATHROOM
 HALLWAY AND DIRECTIONAL EXIT SIGN IN BATHROOM HALLWAY
 OUTSIDE OF KITCHEN DOOR
 • EMERGENCY LIGHTS ON OUTSIDE OF BUILDING OVER EXIT
 DOORS, IN BATHROOMS, AND IN SMOKE ROOM
 • PLANS NEED TO SHOW TRAVEL DISTANCES, DEAD ENDS, AND
 COMMON PATH
 • CONSTRUCTION TYPE V