Plan Review Stops For Permit 24030174
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 03-28-2024 Cont ID  
Sent By cdorman Date 03-28-2024 Time 14:05 Rev Time 0.00
Received By cdorman Date 03-14-2024 Time 15:55 Sent To  
Notes
2024-04-02 10:01:56.00000SENT PAYMENT REQUEST
2024-03-14 15:55:35.00000REVISION RECVD FLPERMITSHELLONIVO.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 03-06-2024 Cont ID  
Sent By cdorman Date 03-06-2024 Time 16:53 Rev Time 0.00
Received By cdorman Date 03-06-2024 Time 15:45 Sent To  
Notes
2024-03-06 16:52:55.00000SHEET PV-10: AC CURRENT LABEL MUST INDICATE MAXIMUM
 COMBINED INVERTER OUTPUT OS 25.41 AMPS WITHOUT THE
 ADDITION OF ANY DEMAND FACTORS. 125% DEMAND FACTORS ARE
 TO BE APPLIED ONLY IN SIZING OVERCURRENT PROTECTION,
 EQUIPMENT RATINGS, AND CONDUCTOR SIZES, SEE 690.54.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET, NOT THE
 ENTIRE PLANSET.