-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24020600
Plan Review Stops For Permit 24020600
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 03-21-2024 Cont ID  
Sent By cdorman Date 03-21-2024 Time 14:02 Rev Time 0.00
Received By cdorman Date 03-04-2024 Time 12:48 Sent To  
Notes
2024-03-04 12:49:19.00000EMAILED IN FROM OSCAR.UMANA@MOMENTUMSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 02-21-2024 Cont ID  
Sent By cdorman Date 02-21-2024 Time 15:30 Rev Time 0.00
Received By cdorman Date 02-16-2024 Time 15:18 Sent To  
Notes
2024-02-21 15:30:20.00000SHEET PV3.2: AC CURRENT LABEL TO SHOW ACTUAL MAXIMUM
 COMBINED INVERTER OUTPUT OF 27.83A. DO NOT ADD DEMAND
 FACTOR TO THIS VALUE; THE ADDITION OF A 25% DEMAND
 FACTOR IS INTENDED FOR SIZING CONDUCTORS, EQUIPMENT,
 AND OVERCURRENT PROTECTION ONLY.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET PV 3.2, NOT
 THE ENTIRE PLAN SET.
2024-02-16 15:19:23.00000OSCAR.UMANA@MOMENTUMSOLAR.COM FOR
 FLPERMITS@MOMENTUMSOLAR.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved