-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24020568
Plan Review Stops For Permit 24020568
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 06-14-2024 Cont ID  
Sent By cdorman Date 06-14-2024 Time 14:03 Rev Time 0.00
Received By cdorman Date 06-06-2024 Time 09:56 Sent To  
Notes
2024-06-06 09:57:11.00000PERMITTING@MYEQUITYSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 04-18-2024 Cont ID  
Sent By cdorman Date 04-18-2024 Time 13:28 Rev Time 0.00
Received By cdorman Date 04-01-2024 Time 11:54 Sent To  
Notes
2024-04-19 08:45:19.00000SENT REVISED PLANS
2024-04-01 11:55:12.00000PERMITTING@MYEQUITYSOLAR.COM SENT REVISED PLANS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 03-14-2024 Cont ID  
Sent By cdorman Date 03-14-2024 Time 15:53 Rev Time 0.00
Received By cdorman Date 02-28-2024 Time 15:10 Sent To  
Notes
2024-02-28 15:10:26.00000PERMITTING@MYEQUITYSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 02-21-2024 Cont ID  
Sent By cdorman Date 02-21-2024 Time 15:15 Rev Time 0.00
Received By cdorman Date 02-16-2024 Time 11:35 Sent To  
Notes
2024-02-21 15:15:35.000001] PROVIDE SPECIFICATION SHEET FOR "MICROGRID
 INTERCONNECTION DEVICE" (ENPHASE SWITCH)
 2] SHOW DISCONNECTING MEANS, READILY ACCESSIBLE AND
 EFFECTIVELY LABELED, FOR BATTERIES ON EXTERIOR OF HOUSE
 3] REPLACE CONDUCTORS BETWEEN ENPHASE SWITCH AND FIRST
 BATTERY TO MINIMUM #8 CU. CONDUCTORS MUST HAVE A
 MINIMUM AMPACITY OF 40 AT 75 DEGREES C.
2024-02-16 11:35:26.00000SENT EMAIL FOR VALUATION AND PLAN REVIEW FEE.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved