Plan Review Details - Permit 24020534
Plan Review Stops For Permit 24020534
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 03-14-2024 Cont ID  
Sent By cdorman Date 03-14-2024 Time 15:52 Rev Time 0.00
Received By cdorman Date 02-27-2024 Time 13:02 Sent To  
Notes
2024-03-18 08:31:45.00000SENT PAYMENT REQ 3/18
2024-02-27 13:02:53.00000REVISION LISA.KNOTE@MOMENTUMSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 02-21-2024 Cont ID  
Sent By cdorman Date 02-21-2024 Time 14:18 Rev Time 0.00
Received By cdorman Date 02-15-2024 Time 14:46 Sent To  
Notes
2024-02-21 14:18:30.00000SHEET PV3.2: AC CURRENT LABEL TO SHOW ACTUAL MAXIMUM
 COMBINED INVERTER OUTPUT OF 19.36A. DO NOT ADD DEMAND
 FACTOR TO THIS VALUE; THE ADDITION OF A 25% DEMAND
 FACTOR IS INTENDED FOR SIZING CONDUCTORS, EQUIPMENT,
 AND OVERCURRENT PROTECTION ONLY.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET PV 3.2, NOT
 THE ENTIRE PLAN SET.