-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 24020400
Plan Review Stops For Permit 24020400
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 03-14-2024 Cont ID  
Sent By cdorman Date 03-14-2024 Time 15:52 Rev Time 0.00
Received By cdorman Date 02-27-2024 Time 12:19 Sent To  
Notes
2024-03-18 08:28:46.00000SENT PAYMENT REQ 3/18
  
2024-02-27 12:19:55.00000LISA.KNOTE@MOMENTUMSOLAR.COM FOR
 FLPERMITS@MOMENTUMSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 02-13-2024 Cont ID  
Sent By cdorman Date 02-13-2024 Time 15:55 Rev Time 0.00
Received By cdorman Date 02-13-2024 Time 14:13 Sent To  
Notes
2024-02-13 15:55:19.00000SHEET PV-3.2: SHOW AC CURRENT LABEL VALUE AS 43.56A,
 NOT 54.45A. CURRENT VALUES SHOULD BE INDICATED AS
 MAXIMUM COMBINED INVERTER OUTPUT WITHOUT THE ADDITION
 OF DEMAND FACTORS. REFERENCE 690.54.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET, NOT THE
 ENTIRE PLANSET.
2024-02-13 14:13:39.00000OSCAR.UMANA@MOMENTUMSOLAR.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved