Plan Review Details - Permit 24010522
Plan Review Stops For Permit 24010522
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status A Date 05-02-2024 Cont ID  
Sent By cdorman Date 05-02-2024 Time 15:57 Rev Time 0.00
Received By cdorman Date 04-23-2024 Time 11:16 Sent To  
Notes
2024-05-03 08:39:29.00000SENT PAYMENT REQ.
2024-04-23 11:16:41.00000RECEIVED UPDATED PLANS VIA EMAIL FROM
 PERMITS@WEARESOLARPOWERUS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status D Date 04-17-2024 Cont ID  
Sent By cdorman Date 04-17-2024 Time 14:41 Rev Time 0.00
Received By cdorman Date 04-15-2024 Time 09:02 Sent To  
Notes
2024-04-17 14:41:18.00000SHEET E-1: SHOW EXISTING FEEDER CONDUCTOR SIZE BETWEEN
 SERVICE AND INTERIOR LOAD CENTER; SHOW RATING OF MAIN
 BREAKER SIZE IN INTERIOR LOAD CENTER. THE PV
 INTERCONNECTION SHOWN IS A FEEDER TAP, AND AS SUCH,
 MUST COMPLY WITH 705.12 (B)(1) (A) OR (B).
 OVERCURRENT DEVICES IN THE EXISTING INTERIOR LOAD
 CENTER WILL BE SUPPLIED BY BOTH UTILITY AND SOLAR; AS
 SUCH, THE FEEDERS SUPPLYING THIS LOAD CENTER MUST BE
 PROTECTED ACCORDING TO THEIR AMPACITY OR MUST BE RATED
 FOR THE SUM OF THE FEEDER SUPPLY BREAKER PLUS 125% OF
 THE SOLAR OUTPUT CURRENT.
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 03-06-2024 Cont ID  
Sent By cdorman Date 03-06-2024 Time 13:33 Rev Time 0.00
Received By cdorman Date 02-29-2024 Time 08:41 Sent To  
Notes
2024-04-15 08:57:52.00000REVISION SENT IN FROM PERMITS@WEARESOLARPOWERUS.COM,
 CHANGE MADE AFTER INSTALL.
2024-03-06 13:26:39.000001] SHEET E-1: SHOW EXISTING FEEDER CONDUCTOR SIZE
 BETWEEN SERVICE AND INTERIOR LOAD CENTER; SHOW ANY
 EXISTING MAIN BREAKER SIZE IN INTERIOR LOAD CENTER. THE
 PV INTERCONNECTION SHOWN IS A FEEDER TAP, AND AS SUCH,
 MUST COMPLY WITH 705.12 (B)(1).
 2] SHEET E-4: AC CURRENT LABEL AT THE MAIN SERVICE
 PANEL MUST SHOW THE COMBINED PV OUTPUT FROM BOTH
 EXISTING AND PROPOSED SYSTEMS (32.93A). THE AC CURRENT
 LABEL FOR THE PROPOSED PV SYSTEM DISCONNECT MAY SHOW
 THE OUTPUT OF THE PROPOSED SYSTEM ONLY (12.1 A).
2024-02-29 08:42:14.00000PERMITS@WEARESOLARPOWERUS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-07-2024 Cont ID  
Sent By cdorman Date 02-07-2024 Time 15:57 Rev Time 0.00
Received By cdorman Date 02-07-2024 Time 09:29 Sent To  
Notes
2024-02-07 09:30:04.00000EMAILED BY WENDY� DE LA VEGA
 

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 01-23-2024 Cont ID  
Sent By cdorman Date 01-23-2024 Time 13:09 Rev Time 0.00
Received By cdorman Date 01-18-2024 Time 08:34 Sent To  
Notes
2024-01-23 13:08:55.00000PLANS AND ENGINEERING DOCUMENTS MUST REFERENCE 2023 FBC
 (8TH EDITION) AND 2020 NEC.
2024-01-18 08:35:44.00000EMAILED IN FROM W.DELAVEGA@WEARESOLARPOWERUS.COM