Plan Review Stops For Permit 23120808
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-22-2024 Cont ID  
Sent By elongsho Date 02-22-2024 Time 08:30 Rev Time 0.00
Received By elongsho Date 01-31-2024 Time 13:51 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 01-16-2024 Cont ID  
Sent By hlopez Date 01-16-2024 Time 16:59 Rev Time 0.00
Received By hlopez Date 12-28-2023 Time 13:45 Sent To  
Notes
2024-01-16 17:00:18.00000PLAN REVIEW NOTES: PERMIT #23120808
  
 I HAVE REVIEWED THESE PLANS AND THEN PLANS WILL NEED TO
 BE REVISED TO ADDRESS THE FOLLOWING COMMENTS.
  
 1. THE PLANS WILL NEED TO BE NOTED THAT THE ELECTRICAL
 DEVICES IN THE EXAM ROOMS WILL NEED TO BE INSTALLED TO
 MEET NEC 517.13 REGULATIONS FOR “PATIENT CARE”
 LOCATIONS.
 2. THE DOOR ENTERING BATHROOM #2 WILL MAY NEED TO BE
 REVISED. PLANS DO NOT SHOW MEASUREMENT FROM THE DOOR TO
 THE ADJACENT MECHANICAL CLOSET WALL. THIS DISTANCE MUST
 BE A MINIMUM OF 54”.
 3. AS NOTED IN THE FIRE MARSHALS REPORT, THE FIRE
 EXTINGUISHERS NEED TO BE RELOCATED TO THE EXITS.
 4. THE FIRE MARSHAL ALSO HAS NOTED THAT ADDITIONAL
 EMERGENCY LIGHTING BE ADDED ON THE EXTERIOR AT THE
 EXITS.
 5. ADDITIONAL EMERGENCY LIGHTING IS ALSO NEEDED IN THE
 PROVIDER OFFICE, THE CONFERENCE ROOM, 2 STAFF OFFICES
 AND THE NORTH CORRIDOR.
 6. ADDITIONAL EXIT SIGNAGE NEEDS TO BE ADDED IN THE
 EAST CORRIDOR AT SOUTH END DOOR TO FRONT LOBBY. THIS
 NEEDS TO BE A COMBINATION EMERGENCY/EXIT LIGHT.
 7. A DIRECTIONAL EXIT SIGN NEEDS TO BE ADDED IN THE
 WEST CORRIDOR AT THE SOUTH END DIRECTING TO THE LOBBY
 AREA.
 8. THERE IS ALSO A QUESTION IF THERE IS ROOM FOR A 36”
 GRAB BAR AT THE REAR OF THE WATER CLOSET IN BATHROOM #2
 DUE TO THE WINDOW.
 ERIC R. LONGSHORE
 BUILDING OFFICIAL
  

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status C Date 12-28-2023 Cont ID  
Sent By cshackel Date 12-28-2023 Time 13:47 Rev Time 0.00
Received By cshackel Date 12-28-2023 Time 13:45 Sent To  
Notes
2023-12-28 13:48:32.00000FINAL DEVELOPMENT ORDER CONDIIONALLY APPROVED BY ENG ON
 NOV. 29, 2023 REFERENCE NO. 23060006 SCANNED INTO
 ONBASE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status A Date 02-15-2024 Cont ID  
Sent By hlopez Date 02-15-2024 Time 15:08 Rev Time 0.00
Received By hlopez Date 01-31-2024 Time 13:52 Sent To  
Notes
2024-02-15 15:08:25.00000PLAN REVIEW #: 23120808
  
 PROJECT: SUN N LAKE MEDICAL - ADDITION
  
 LOCATION: 5100 SUN N LAKE BLVD
  
 OCCUPANCY: BUSINESS
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED - PLANS CORRECTED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status D Date 01-16-2024 Cont ID  
Sent By hlopez Date 01-16-2024 Time 08:50 Rev Time 0.00
Received By hlopez Date 12-28-2023 Time 13:45 Sent To  
Notes
2024-01-16 16:11:17.00000REJECTED,, PICKED UP BY MARMAR KRYSTAL... 01/16/2024
2024-01-16 08:51:00.00000PLAN REVIEW #: 23120808
  
 PROJECT: SUN N LAKE MEDICAL - ADDITION
  
 LOCATION: 5100 SUN N LAKE BLVD
  
 OCCUPANCY: BUSINESS
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED NEED MORE INFORMATION/PLANS CORRECTED
  
 MOVE FIRE EXTINGUISHER TO EXITS
 EMERGENCY LIGHTS ADDED TO EXTERIOR AT ALL EXITS
 EMERGENCY LIGHTS ADDED TO NURSE STATION, STAFF OFFICES,
 CONFERENCE ROOM, PROVIDER OFFICE, AND HALLWAYS
  
 REVIEW FEE – $140 + INSPECTION FEE $25 = $165
  