-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 23120791
Plan Review Stops For Permit 23120791
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 02-21-2024 Cont ID  
Sent By cdorman Date 02-21-2024 Time 16:31 Rev Time 0.00
Received By cdorman Date 02-07-2024 Time 15:06 Sent To  
Notes
2024-02-07 15:07:03.00000REVISION EMAILED IN BY FL PERMIT

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 02-06-2024 Cont ID  
Sent By cdorman Date 02-06-2024 Time 16:42 Rev Time 0.00
Received By cdorman Date 02-06-2024 Time 12:49 Sent To  
Notes
2024-02-06 16:42:29.00000SHEET EE-1: INSTALL MAIN BREAKER IN EXISTING INTERIOR
 PANEL TO LIMIT CURRENT TO 200 AMPS (BUS RATING); SHOW
 SIZE OF EXISTING FEEDER CONDUCTORS BETWEEN SERVICE AND
 INTERIOR PANEL; THESE CONDUCTORS MUST HAVE AN AMPACITY
 NOT LESS THAN THE RATING OF THE NEW MAIN BREAKER. SEE
 705.12 (B)(2)(1) OF 2017 NEC.
 SHEET EE-3: INDICATE ACTUAL MAXIMUM COMBINED INVERTER
 OUTPUT ON AC CURRENT LABEL (56.87A).
2024-02-06 12:50:08.00000EMAILED IN BY FL PERMIT

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 01-17-2024 Cont ID  
Sent By cdorman Date 01-17-2024 Time 15:57 Rev Time 0.00
Received By cdorman Date 01-03-2024 Time 14:22 Sent To  
Notes
2024-01-18 08:16:06.00000SENT PAYMENT REQUEST 1/18
2024-01-03 14:23:22.00000FLPERMIT@KINHOME.COM EMAILED IN THE REVISED PAGE
 REQUESTED BY PLAN REVIEWER. 01/03/2024

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 12-28-2023 Cont ID  
Sent By cdorman Date 12-28-2023 Time 12:36 Rev Time 0.00
Received By cdorman Date 12-28-2023 Time 09:43 Sent To  
Notes
2023-12-28 12:36:26.00000SHEET EE3: CHANGE AC CURRENT LABEL TO SHOW 56.87.
 PLEASE SUBMIT ONLY A REVISED SHEET EE3, NOT ENTIRE PLAN
 SET.
2023-12-28 09:43:56.00000FLPERMIT@KINHOME.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved