-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 23110808
Plan Review Stops For Permit 23110808
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 12-20-2023 Cont ID  
Sent By cdorman Date 12-20-2023 Time 08:43 Rev Time 0.00
Received By cdorman Date 12-19-2023 Time 08:29 Sent To  
Notes
2023-12-20 11:31:23.00000SENT REQUEST FOR PAYMENT
2023-12-19 08:30:04.00000EMAILED REVISION PER 1ST REVIEW -
 CCHAVEZ@SCOUTSERVICES.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-29-2023 Cont ID  
Sent By cdorman Date 11-29-2023 Time 16:27 Rev Time 0.00
Received By cdorman Date 11-29-2023 Time 08:51 Sent To  
Notes
2023-11-29 16:27:31.00000SHEET C1.3: SHOW CIRCUIT DATA FOR THREE PROPOSED
 WALL-MOUNT DISPENSERS.
 SHEET E2.1: REWORK PANEL SCHEDULE SUMMARY. THE
 FOLLOWING VALUES DO NOT CORRESPOND TO THE INDICATED
 CONNECTED LOAD: TOTAL KVA PER PHASE; TOTAL AMPS PER
 PHASE; TOTAL CONNECTED KVA; TOTAL CONNECTED AMPS; KVA
 AND AMP TOTALS AFTER CONTINUOUS FACTOR ADDED.
2023-11-29 08:51:51.00000CCHAVEZ@SCOUTSERVICE.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved