Plan Review Stops For Permit 23110620
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 02-21-2024 Cont ID  
Sent By cdorman Date 02-21-2024 Time 16:30 Rev Time 0.00
Received By cdorman Date 02-02-2024 Time   Sent To  
Notes
2024-02-23 08:45:08.00000SENT REVISED PLANS 02/23
2024-02-02 11:37:40.00000REVISION REQUEST: DANIELA.OROZCO@GOSUNERGY.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 12-13-2023 Cont ID  
Sent By cdorman Date 12-13-2023 Time 14:33 Rev Time 0.00
Received By cdorman Date 11-28-2023 Time 15:54 Sent To  
Notes
2023-12-19 08:35:35.00000SENT PAYMENT REQUEST 12/19
  
2023-11-28 15:55:16.00000SENT NEW PLANS DANIELA OROZCO
 

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-20-2023 Cont ID  
Sent By cdorman Date 11-20-2023 Time 10:12 Rev Time 0.00
Received By cdorman Date 11-20-2023 Time 08:29 Sent To  
Notes
2023-11-20 10:12:49.00000SHEET E003: SHOW SIZE OF EXISTING FEEDER CONDUCTORS
 BETWEEN SERVICE AND INTERIOR PANEL. USING A FEEDER TAP
 AS SHOWN, INSTALLATION MUST COMPLY WITH 705.12
 (B)(2)(1): THAT PORTION OF THE FEEDER ON THE LOAD SIDE
 OF THE PV INTERCONNECTION SHALL BE PROTECTED BY 1]
 HAVING AN AMPACITY EQUAL TO 125% OF THE PV OUTPUT
 (39.33) PLUS THE RATING OF THE OVERCURRENT DEVICE
 PROTECTING THE FEEDER (125A) OR 2] BY AN OVERCURRENT
 DEVICE ON THE LOAD SIDE OF THE PV INTERCONNECTION RATED
 NOT GREATER THAN THE AMPACITY OF THE FEEDER.
 IF POSSIBLE, SUBMIT ONLY REVISED SHEET E003, NOT ENTIRE
 PLANSET
2023-11-20 08:33:26.00000DANIELA.OROZCO@GOSUNERGY.COM