Plan Review Details - Permit 23110517
Plan Review Stops For Permit 23110517
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 12-21-2023 Cont ID  
Sent By cdorman Date 12-21-2023 Time 08:18 Rev Time 0.00
Received By cdorman Date 12-05-2023 Time 08:49 Sent To  
Notes
2023-12-05 08:50:17.00000SENT CORRECTIONS
 PERMITTING MYEQUITYSOLAR.COM
 

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-20-2023 Cont ID  
Sent By cdorman Date 11-20-2023 Time 10:00 Rev Time 0.00
Received By cdorman Date 11-15-2023 Time 10:36 Sent To  
Notes
2023-11-20 09:53:26.00000SHEET PV4 DOES NOT DEPICT AN EXTERIOR DISCONNECT SWITCH
 TO INITIATE PV ARRAY RAPID SHUTDOWN AND ESS STANDBY
 MODE. SINCE THE IQ CONTROLLER 2 IS DESIGNED TO ISLAND,
 OPENING THE 100-AMP FUSED DISCONNECT WILL NOT INITIATE
 PV RAPID SHUTDOWN OR PUT THE ENCHARGE 10T INTO STANDBY
 MODE.
 ALL OTHER DESIGN CONSIDERATIONS AND VALUES ARE
 COMPLIANT.
  
 CORRECTION REQUIRED: INSTALL BATTERY DISCONNECT (OR
 REMOTE CONTROL SYSTEM SHUTDOWN SWITCH) ON EXTERIOR OF
 HOUSE AND APPLY APPROPRIATE LABEL TO SAME.
 IF POSSIBLE, SUBMIT ONLY SHEET PV4, NOT ENTIRE PLAN
 SET.
2023-11-15 10:37:11.00000EMAILED 11/1 AND NOT ENTERED