Plan Review Stops For Permit 23110413
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-14-2023 Cont ID  
Sent By cdorman Date 11-14-2023 Time 15:24 Rev Time 0.00
Received By cdorman Date 11-13-2023 Time 13:51 Sent To  
Notes
2023-11-14 15:24:23.000001] SHEET E003: SHOW SIZE OF FEEDER CONDUCTORS BETWEEN
 SERVICE AND INTERIOR PANEL(S); SHOW OVERCURRENT
 PROTECTION FOR INTERIOR PANELS. AS A FEEDER-TAP
 INTERCONNECTION, THE INSTALLATION MUST COMPLY WITH
 705.12 (B)(2)(1): THAT PORTION OF THE FEEDER ON THE
 LOAD SIDE OF THE PV INTERCONNECTION SHALL BE PROTECTED
 BY 1) AN AMPACITY NOT LESS THAN THE SUM OF THE 125A
 SOURCE PLUS 125% OF THE PV OUTPUT, OR 2) OVERCURRENT
 PROTECTION ON THE LOAD SIDE OF THE PV INTERCONNECTION
 RATED NOT GREATER THAN THE AMPACITY OF THE FEEDER.
  
 2] SHEET E005: CHANGE AC CURRENT LABEL TO SHOW 13.31
 AMPS