Plan Review Details - Permit 23110001
Plan Review Stops For Permit 23110001
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status A Date 11-15-2023 Cont ID  
Sent By cdorman Date 11-15-2023 Time 16:13 Rev Time 0.00
Received By cdorman Date 11-06-2023 Time 13:12 Sent To  
Notes
2023-11-16 12:24:34.00000SENT EMAIL TO PAY FOR PERMIT
2023-11-06 13:13:22.00000DANIELA.OROZCO@GOSUNERGY.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-01-2023 Cont ID  
Sent By cdorman Date 11-01-2023 Time 16:29 Rev Time 0.00
Received By cdorman Date 11-01-2023 Time 07:49 Sent To  
Notes
2023-11-01 16:28:50.00000SHEET E003: SEE 705.12 (B)(2)(1). UNKNOWN SIZE OF
 EXISTING FEEDERS SUPPLYING INTERIOR PANEL. THESE
 FEEDERS MUST HAVE AN AMPACITY OF AT LEAST 125% OF THE
 PV INPUT PLUS 125 AMPS (SERVICE BREAKER) OR THE MAIN
 BREAKER IN THE INTERIOR PANEL MUST BE RATED NO MORE
 THAN THE FEEDER AMPACITY.
2023-11-01 07:49:55.00000DANIELA.OROZCO@GOSUNERGY.COM