Plan Review Details - Permit 23100682
Plan Review Stops For Permit 23100682
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 01-11-2024 Cont ID  
Sent By cdorman Date 01-11-2024 Time 13:46 Rev Time 0.00
Received By cdorman Date 12-27-2023 Time 15:36 Sent To  
Notes
2024-01-11 15:12:10.00000SENT REVISED PLANS 1/11
2023-12-27 15:38:03.00000REVISION REQUEST EMAILED IN 12/27
 KELCIE@CASTAWAYSENERGY.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 12-20-2023 Cont ID  
Sent By cdorman Date 12-20-2023 Time 08:56 Rev Time 0.00
Received By cdorman Date 12-15-2023 Time 10:34 Sent To  
Notes
2023-12-20 08:56:47.000001] NEW VALUATION REQUIRED DUE TO ADDITION OF ENERGY
 STORAGE SYSTEM. PROVIDE STATEMENT OF REVISED VALUATION
 ON COMPANY LETTERHEAD.
 2] SHEETS A101 & E601: A READILY ACCESSIBLE AND
 PERMANENTLY IDENTIFIED DISCONNECTING MEANS IS REQUIRED
 ON OR WITHIN SIGHT OF THE ENERGY STORAGE DEVICES. (NOTE
 THAT 2020 NEC REQUIRES THIS DISCONNECTING MEANS TO BE
 ON THE EXTERIOR OF THE HOUSE). REFER TO 2017 NEC 706.7
 (A).
 THE TESLA FACTORY-INSTALLED SWITCH ON EACH BATTERY IS
 ACCEPTABLE FOR THIS PURPOSE PROVIDED THAT IT IS CLEARLY
 AND PERMANENTLY IDENTIFIED PER 2017 NEC 706.7 (E)(5).
 NOTE THAT THIS IDENTIFICATION MUST INCLUDE A DIRECTORY
 OR PLACARD AT ALL DISCONNECTING MEANS (ESS & TESLA
 SWITCH) SHOWING THE LOCATION OF EVERY BATTERY
 DISCONNECTING MEANS.
2023-12-15 10:34:42.00000REVIEW SENT IN 12/14/23

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 11-09-2023 Cont ID  
Sent By cdorman Date 11-09-2023 Time 15:37 Rev Time 0.00
Received By cdorman Date 10-23-2023 Time 13:16 Sent To  
Notes
2023-11-13 10:28:01.00000SENT EMAIL TO PAY
2023-10-23 13:17:05.00000EMAILED BY KELCIE FERMINO