-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 23090709
Plan Review Stops For Permit 23090709
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 11-22-2023 Cont ID  
Sent By cdorman Date 11-22-2023 Time 15:54 Rev Time 0.00
Received By cdorman Date 11-22-2023 Time 08:51 Sent To  
Notes
2023-11-22 15:54:10.00000SHEET E003: REVISE ONE-LINE DIAGRAM. THE
 INTERCONNECTION POINT IS A FEEDER TAP, NOT A
 SUPPLY-SIDE TAP. DO NOT SHOW BONDING OF
 NEUTRAL-TO-GROUND IN PV DISCONNECT.
 IF POSSIBLE, SUBMIT ONLY REVISED SHEET E003, NOT ENTIRE
 PLANSET.
2023-11-22 08:51:30.00000REVISED MOUNTS STACY.AMEROSA@GOSUNERGY.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 10-12-2023 Cont ID  
Sent By cdorman Date 10-12-2023 Time 14:42 Rev Time 0.00
Received By cdorman Date 09-21-2023 Time 16:38 Sent To  
Notes
2023-10-13 11:44:34.00000SENT A PAYMENT REQUEST 10/13
2023-09-21 16:38:59.00000EMAILED IN BY STACY AMEROSA
 

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved