Plan Review Details - Permit 23090358
Plan Review Stops For Permit 23090358
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 10-05-2023 Cont ID  
Sent By cdorman Date 10-05-2023 Time 15:21 Rev Time 0.00
Received By cdorman Date 09-13-2023 Time 12:55 Sent To  
Notes
2023-10-06 11:34:07.00000EMAILED FOR PAYMENT
2023-09-19 12:37:18.00000REVISED PLANS RECEIVED 09/19/23
2023-09-14 08:24:32.00000SHEET E003: EQUIPMENT GROUNDING CONDUCTOR BETWEEN NEW
 LOAD CENTER AND PV DISCONNECT MUST BE #6 CU (CONDUCTOR
 ID #4). THIS INTERCONNECTION IS A FEEDER TAP CONNECTED
 ON THE LOAD SIDE OF A 125A OCPD; TABLE 250.122 APPLIES.
 IF POSSIBLE, SEND REVISED SHEET E003 ONLY, DO NOT SEND
 ENTIRE PLANSET.