Plan Review Details - Permit 23080704
Plan Review Stops For Permit 23080704
Review Stop BLDREN REISSUANCE BUILDING PERMIT
Rev No 1 Status A Date 06-11-2024 Cont ID  
Sent By cbrooks Date 06-11-2024 Time 14:33 Rev Time 0.00
Received By cbrooks Date 06-11-2024 Time 14:33 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 08-29-2023 Cont ID  
Sent By cshackel Date 08-29-2023 Time 08:19 Rev Time 0.00
Received By cshackel Date 08-28-2023 Time 13:59 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-23-2023 Cont ID  
Sent By cdorman Date 08-23-2023 Time 16:40 Rev Time 0.00
Received By cdorman Date 08-21-2023 Time 08:07 Sent To  
Notes
2023-08-23 16:40:48.000001] TRANSFORMER SECONDARY SHOULD SHOW (3) SETS OF 4 400
 KCMIL, NOT (3) SETS OF 3 400 KCMIL. A NEUTRAL MUST BE
 INCLUDED IN THESE CONDUCTOR SETS.
 2] SHOW 2/0 GROUNDS (SUPPLY-SIDE BONDING JUMPERS) IN
 TRANSFORMER SECONDARY CONDUCTOR SETS AS COPPER. IF
 USING ALUMINUM, INCREASE TO 4/0 IN EACH SET. SEE TABLE
 250.102 (C)(1).
 3] SHOW #3 EQUIPMENT GROUNDING CONDUCTOR IN TRANSFORMER
 PRIMARY CONDUCTOR SETS AS COPPER. IF USING ALUMINUM,
 INCREASE TO #1 IN EACH SET. SEE TABLE 250.122.
 4] SHOW GROUNDING ELECTRODE CONDUCTOR FROM TRANSFORMER
 BONDED TO GROUNDING ELECTRODE SYSTEM AT MAIN 480V
 SERVICE PANEL. SEE 250.30 (A) (4).
 5] PROVIDE BONDING/GROUNDING DETAIL FOR TRANSFORMER
 (INTERIOR CONNECTIONS DETAIL FOR ALL
 GROUNDING/BONDING).
2023-08-21 08:08:59.00000A.TENNEY@TE-FL.COM