-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 23080440
Plan Review Stops For Permit 23080440
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 11-30-2023 Cont ID  
Sent By cdorman Date 11-30-2023 Time 15:02 Rev Time 0.00
Received By cdorman Date 11-16-2023 Time 12:16 Sent To  
Notes
2023-12-04 08:58:30.00000SENT APPROVED PLANS.
2023-11-16 12:17:09.00000MATTHEW.WILSON@LUMIO.COM REVISION COMMENTS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 11-09-2023 Cont ID  
Sent By cdorman Date 11-09-2023 Time 15:56 Rev Time 0.00
Received By cdorman Date 11-09-2023 Time 10:05 Sent To  
Notes
2023-11-09 15:56:32.00000SHEET E002: SHOW 50A OVERCURRENT PROTECTION IN PV
 DISCONNECT. 33 X 1.21 X 1.25 = 49.91.
 IF POSSIBLE, SEND REVISED SHEET E002 ONLY, NOT ENTIRE
 PLANSET.
2023-11-09 10:06:08.00000SENT REVISION MATTHEW.WILSON@LUMIO.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 08-31-2023 Cont ID  
Sent By cdorman Date 08-31-2023 Time 15:13 Rev Time 0.00
Received By cdorman Date 08-14-2023 Time 08:15 Sent To  
Notes
2023-09-05 10:44:53.00000SENT EMAIL TO PAY FOR PERMIT
2023-08-14 08:15:42.00000TIFFANY.LIMAPO@LUMIO.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved