Plan Review Details - Permit 23080184
Plan Review Stops For Permit 23080184
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 09-15-2023 Cont ID  
Sent By cdorman Date 09-15-2023 Time 16:36 Rev Time 0.00
Received By cdorman Date 09-01-2023 Time 10:35 Sent To  
Notes
2023-09-18 13:05:27.00000SENT APPROVED PLANS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 08-16-2023 Cont ID  
Sent By cdorman Date 08-16-2023 Time 12:06 Rev Time 0.00
Received By cdorman Date 08-15-2023 Time 08:08 Sent To  
Notes
2023-08-16 12:06:44.00000PREVIOUS DEFICIENCY NOT CORRECTED. SEE SHEET E-003,
 CONDUCTOR SET #4. GROUNDING CONDUCTOR BETWEEN FEEDER
 TAP AND PV DISCONNECT MUST BE MINIMUM #8 COPPER.
2023-08-15 08:11:13.00000DANIELA OROZCO

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amhernan Date 08-07-2023 Time 10:12 Sent To  
Notes
2023-09-18 08:33:41.00000SENT PAYMENT REQUEST 9/18
2023-08-09 16:19:59.00000SHEET E003: INSTALL #8 BONDING CONDUCTOR BETWEEN LOAD
 SIDE (FEEDER) TAP AND PV DISCONNECT. DO NOT BOND
 NEUTRAL IN PV DISCONNECT. SEE TABLE 250.102 (C)(1) AND
 250.24 (A)(5).
 SUBMIT REVISED E003 OR REVISED SOLAR PLAN SET SHOWING
 CORRECTION.
2023-08-04 09:40:53.00000DANIELA OROZCO