-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 23080079
Plan Review Stops For Permit 23080079
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 08-29-2023 Cont ID  
Sent By cdorman Date 08-29-2023 Time 15:44 Rev Time 0.00
Received By cdorman Date 08-29-2023 Time 13:04 Sent To  
Notes
2023-08-29 13:05:20.00000SHANNONMAY2MAYELECTRIC.NET

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-02-2023 Cont ID  
Sent By cdorman Date 08-02-2023 Time 13:30 Rev Time 0.00
Received By cdorman Date 08-02-2023 Time 10:10 Sent To  
Notes
2023-08-16 16:02:47.00000USE CIVITEK RECEIPT 8668438 FOR 195.78 THEN LET SHANNON
 KNOW HOW MUCH ADDITIONAL SHE OWES FOR THE PAYMENT OF
 THIS PERMIT - SEE ATTACHMENT COPY OF RECEIPT
2023-08-02 13:30:45.00000SHEET 1 (RISER DIAGRAM):
 1] RE-IDENTIFY "SERVICE LATERAL" AS A FEEDER.
 2] ADD #6 CU EQUIPMENT GROUNDING CONDUCTOR TO FEEDER
 SET
 3] INCREASE FEEDER UNGROUNDED CONDUCTORS TO 3/0 CU OR
 DECREASE PROPOSED SERVICE DISCONNECT TO 175A RATING.
 (MAXIMUM AMPACITY OF PROPOSED 2/0 CU IS 175A). THIS
 APPLIES TO ALL FEEDER CONDUCTORS BETWEEN PROPOSED
 SERVICE AND PROPOSED DISTRIBUTION PANEL, AND WILL ALSO
 APPLY TO THE BLOWER CONTROL PANEL CONDUCTORS
 ORIGINATING IN THE DISTRIBUTION PANEL, UNLESS
 OVERCURRENT PROTECTION IS PROVIDED ON THE LOAD END OF
 THESE CONDUCTORS AS A FEEDER TAP PER 240.21 (B)(5).
 4] AS AN ALTERNATIVE TO ITEM #3, PROVIDE A SPECIFIC
 LOAD SUMMARY SHOWING COMPLIANCE WITH 430.24 (FOR 2/0
 CU) AND WITH 430.62 (FOR 200A BREAKER).
2023-08-02 10:11:08.00000SHANNONMARY2MAYELECTRIC.NET

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved