Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 08-31-2023 Cont ID  
Sent By cdorman Date 08-31-2023 Time 15:12 Rev Time 0.00
Received By cdorman Date 08-15-2023 Time 15:35 Sent To  
Notes
2023-09-06 12:14:09.00000SENT PAYMENT REQUEST 9/06
2023-08-15 15:35:31.00000RCVD REVISED PLANS THAT WERE REQUESTED BY PLANS
 EXAMINER PERMITTING@MYEQUITYSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-02-2023 Cont ID  
Sent By cdorman Date 08-02-2023 Time 15:08 Rev Time 0.00
Received By cdorman Date 08-01-2023 Time 16:00 Sent To  
Notes
2023-08-02 15:08:31.00000SHEET PV4: PV DISCONNECT MUST BE LOCATED ON EXTERIOR OF
 ONE-FAMILY DWELLING TO FUNCTION AS REQUIRED RAPID
 SHUTDOWN SWITCH, 690.12 (C). REMOVE #10 EGC BETWEEN PV
 DISCONNECT AND SUPPLY-SIDE TAP; USE NEUTRAL CONDUCTOR
 FOR SYSTEM BONDING IN PV DISCONNECT.