Plan Review Details - Permit 23060449
Plan Review Stops For Permit 23060449
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 11-02-2023 Cont ID  
Sent By cdorman Date 11-02-2023 Time 16:20 Rev Time 0.00
Received By cdorman Date 10-12-2023 Time 08:06 Sent To  
Notes
2023-11-06 08:45:51.00000SENT REVISED PLANS 11/06
  
2023-10-12 08:06:49.00000REVISED PLANS REQUESTED BY CHUCK RCVD 10/12/23
 PERMITTING@BUSYBEECONTRACTORSERVICES.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 09-14-2023 Cont ID  
Sent By cdorman Date 09-14-2023 Time 16:53 Rev Time 0.00
Received By cdorman Date 09-13-2023 Time 09:08 Sent To  
Notes
2023-09-14 16:53:45.00000SHEET E-1, CLARIFICATIONS AND CORRECTIONS REQUESTED:
 1] POSSIBLE CONFLICT WITH ITEM#16. #12 NOTE INDICATES
 150A BUS RATING; ITEM #16 INDICATES 125A BUS RATING FOR
 SAME PANEL. IT IS ASSUMED THE 150A NOTATION IS
 CALCULATING 120% OF THE 125A BUS RATING, PLEASE CLARIFY
 LANGUAGE.
 2] ADD #8 CU EQUIPMENT GROUNDING CONDUCTOR TO CONDUCTOR
 ID #18, FEEDER WITH 100A O/C PROTECTION.
 3] CORRECT NOTATION OF 150A MSP BUS RATING SHOWN IN
 "SYSTEM DATA" BOX IN LOWER RIGHT QUARTER OF SHEET
 (ASSUMING 125A BUS AS INDICATED ON ONE-LINE).
  
2023-09-13 09:09:00.00000SENT IN 3RD REVISION BEFORE 2ND WAS REVIEWED

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 09-13-2023 Cont ID  
Sent By cdorman Date 09-13-2023 Time 14:27 Rev Time 0.00
Received By cdorman Date 09-01-2023 Time 09:42 Sent To  
Notes
2023-09-01 09:43:10.00000REVISED PLANS EMAILED IN
 PERMITTING@BUSYBEECONTRACTORSERVICES.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 06-27-2023 Cont ID  
Sent By cdorman Date 06-27-2023 Time 14:22 Rev Time 0.00
Received By cdorman Date 06-13-2023 Time 12:38 Sent To  
Notes
2023-06-13 12:38:53.00000EMAILED IN BY TINA GODFREY
 