2023-06-28 16:27:15.000001] CLARIFY TOTAL NUMBER OF CONDUCTORS IN NEW 2" PVC
 CONDUIT TO GUTTER. SIX #2 CU? SHOW CONDUCTORS AS THWN
 (CAN BE DUAL-RATED THHN/THWN)
 2] SHOW MYERS HUB AT PVC CONNECTION ON TOP OF METER
 ENCLOSURE
 3] SHOW BONDING METHOD FOR GUTTER
 4] PROVIDE SPECIFICATION SHEET FOR PROPOSED LUGS TO BE
 INSTALLED IN METER LINE COMPARTMENT.