Plan Review Details - Permit 23060146
Plan Review Stops For Permit 23060146
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 07-19-2023 Cont ID  
Sent By elthomps Date 07-19-2023 Time 15:52 Rev Time 0.00
Received By elthomps Date 07-17-2023 Time 10:23 Sent To  
Notes
2023-07-19 14:02:18.000001] PLEASE CLARIFY IF THE SCOPE OF WORK IS AN ADDTION TO
 AN EXISTING PV SYSTEM.
 2] STRUCTURAL ENGINEERING HAS BEEN RECEIVED AND IS
 APPROVED.
 3] SHEET E-1:
 A) CONDUCTORS BETWEEN SUPPLY-SIDE TAP AND 125A IQ
 CONTROLLER BREAKER MUST HAVE AN AMPACITY NOT LESS THAN
 125A. AMPACITY SELECTION IS PER 75 DEGREE COLUMN OF
 TABLE 310.15 (B)(16). DWELLING UNIT DERATING DOES NOT
 APPLY SINCE THESE CONDUCTORS DO NOT SUPPLY THE ENTIRE
 DWELLING UNIT.
 B) CONDUCTORS ON THE LOAD SIDE OF THE 100A IQ
 CONTROLLER BREAKER MUST HAVE AN AMPACITY NOT LESS THAN
 100A WITH AMPACITY SELECTION AS IN ITEM (A) ABOVE.
 C) CONDUCTORS "B" AND "C" DESCRIPTION IN LEGEND DO NOT
 CORRESPOND TO THEIR POSITIONS IN THE ONE-LINE DIAGRAM.
 D) "OCPD" VALUES IN LEGEND ARE NOT ACCURATE. SHOW
 INTENDED OVERCURRENT PROTECTION VALUE FOR EACH SET OF
 CONDUCTORS.
 REWORK SHEET E-1 AS NECESSARY FOR CODE-COMPLIANCE AND
 CLARITY.
  
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-08-2023 Cont ID  
Sent By cdorman Date 06-08-2023 Time 10:10 Rev Time 0.00
Received By cdorman Date 06-05-2023 Time 13:47 Sent To  
Notes
2023-06-08 10:10:06.000001] PROVIDE OWNER AFFIDAVIT WITH APPLICATION PACKAGE
 (OWNER ACTING AS CONTRACTOR)
 2] SHEET S-2 (DETAILS) AND SHEET S-1A (MOUNTING PLAN):
 PROVIDE PROFESSIONAL ENGINEERING SEAL ON AFFECTED
 SHEETS OR BY SEPARATE DOCUMENT.
 3] SHEET E-1: PROVIDE SEPARATE CONDUITS FOR SUPPLY-SIDE
 TAP CONDUCTORS AND PV INPUT CONDUCTORS (DESIGNATION "A"
 ON PLANS). SUPPLY-SIDE TAPPED CONDUCTORS MUST BE
 CONTAINED IN A RACEWAY WITH NO OTHER CONDUCTORS, NEC
 230.7 APPLIES.
2023-06-07 09:58:42.00000OWNER/BUILDER ELECTRIC STATEMENT HAS BEEN RECEIVED, IT
 IS IN ONBASE ALREADY.
2023-06-05 13:48:09.00000EMAILED IN FROM OWNER BRYANAGARD@MSN.COM
 SENT THEM AN OWNERS/ELECTRIC DISCLOSURE STATEMENT TO
 FILL OUT.