Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-31-2023 Cont ID  
Sent By cdorman Date 05-31-2023 Time 16:31 Rev Time 0.00
Received By cdorman Date 05-31-2023 Time 16:27 Sent To  
Notes
2023-05-31 16:31:33.00000SHEET E01: GROUNDED CONDUCTOR (WHITE WIRE) BETWEEN
 SUPPLY-SIDE TAP AND PV DISCONNECT MUST BE MINIMUM #8 CU
 TO COMPLY WITH TABLE 250.102 (C)(1), SINCE IT IS
 PERFORMING THE FUNCTION OF BONDING THE PV SYSTEM TO
 GROUND. IF INTENDING TO USE #10 UNGROUNDED CONDUCTORS
 FOR SUPPLY-SIDE TAP, PROVIDE DOCUMENTATION OF
 ACCEPTABLE TAP CONDUCTOR SIZES FOR INTENDED TAP DEVICE.
 PLEASE SEND ONLY THE AFFECTED SHEET E01 FOR REVIEW.