Plan Review Details - Permit 23051246
Plan Review Stops For Permit 23051246
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 07-19-2023 Cont ID  
Sent By cdorman Date 07-19-2023 Time 16:27 Rev Time 0.00
Received By cdorman Date 07-03-2023 Time 15:24 Sent To  
Notes
2023-07-03 15:24:51.00000REECVED REQUESTED REVISIONS, PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 06-15-2023 Cont ID  
Sent By cdorman Date 06-15-2023 Time 16:33 Rev Time 0.00
Received By cdorman Date 06-15-2023 Time 13:07 Sent To  
Notes
2023-06-15 16:33:31.00000SHEET E-01: GROUNDED CONDUCTOR (WHITE) BETWEEN
 SUPPLY-SIDE TAP AND PV DISCONNECT MUST BE MINIMUM #8
 CU. SINCE THIS CONDUCTOR WILL BE BONDED IN THE PV
 DISCONNECT, IT SERVES AS THE FAULT CURRENT PATH FOR THE
 SUPPLY-SIDE CONDUCTORS AND MUST BE SIZED PER TABLE
 250.102 (C)(1).
2023-06-15 13:08:19.00000REVISION SENT IN BY PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 06-09-2023 Cont ID  
Sent By cdorman Date 06-09-2023 Time 15:48 Rev Time 0.00
Received By cdorman Date 05-30-2023 Time 16:27 Sent To  
Notes
2023-05-30 16:27:52.00000PERMITS@SUNVENA.COM