Plan Review Stops For Permit 23051141
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-21-2023 Cont ID  
Sent By cdorman Date 06-21-2023 Time 14:42 Rev Time 0.00
Received By cdorman Date 06-06-2023 Time 14:13 Sent To  
Notes
2023-06-06 14:19:34.00000SUNVENA PERMITS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-26-2023 Cont ID  
Sent By cdorman Date 05-26-2023 Time 12:42 Rev Time 0.00
Received By cdorman Date 05-26-2023 Time 07:49 Sent To  
Notes
2023-05-26 12:42:28.00000SHEET E-01: CONDUCTORS BETWEEN PV DISCONNECT AND
 ENPHASE COMBINER PANEL ARE DOUBLE-IDENTIFIED; SHOW
 CORRECT PARAMETERS FOR THIS SET OF CONDUCTORS.
 IDENTIFICATION FOR CONDUCTORS BETWEEN SUPPLY-SIDE TAP
 AND PV DISCONNECT IS MISSING (NOTE THAT THIS MUST BE A
 WIRING METHOD COMPLYING WITH NEC 230.43).
2023-05-26 07:49:49.00000PERMITS@SUNVENA.COM