Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 06-05-2023 Time 13:53 Sent To  
Notes
2023-06-05 13:54:15.00000JACOB.GIVEN@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-25-2023 Cont ID  
Sent By cdorman Date 05-25-2023 Time 14:40 Rev Time 0.00
Received By cdorman Date 05-25-2023 Time 13:51 Sent To  
Notes
2023-05-25 14:40:10.00000SHEET PV06: IN 100A COMBINER PANEL, USE 60A BREAKER
 WITH EXISTING 10KW INVERTER AC OUTPUT.
 SHEET PV08: AC CURRENT LABEL TO SHOW MAXIMUM COMBINED
 SYSTEM OUTPUT (BOTH EXISTING & PROPOSED SYSTEMS) OF 61
 AMPS
2023-05-25 13:52:06.00000EMAILED IN BY