Plan Review Details - Permit 23050703
Plan Review Stops For Permit 23050703
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-23-2023 Cont ID  
Sent By cdorman Date 06-23-2023 Time 15:12 Rev Time 0.00
Received By cdorman Date 06-05-2023 Time 13:55 Sent To  
Notes
2023-06-05 13:55:20.00000REVISED PLANS JABOC.GIVEN@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-17-2023 Cont ID  
Sent By cdorman Date 05-17-2023 Time 14:20 Rev Time 0.00
Received By cdorman Date 05-16-2023 Time 14:12 Sent To  
Notes
2023-05-17 14:20:07.00000SHEET PV 08: CHANGE AC CURRENT LABEL TO REFLECT MAXIMUM
 SYSTEM OUTPUT OF BOTH EXISTING & PROPOSED ARRAYS (36 X
 1.21 = 43.56 AMPS).
 SHEET PV 06: EXPLAIN NOTE ON CONDUCTOR KEY #4 "NO
 GROUND WIRE PRESENT". THIS RACEWAY SHOULD CONTAIN AN
 EQUIPMENT GROUNDING CONDUCTOR, AND THE NEUTRAL SHOULD
 NOT BE RECONNECTED TO GROUND BEYOND THE INITIAL
 SUPPLY-SIDE DISCONNECT, I.E., DO NOT BOND THE NEUTRAL
 IN THE SECOND DISCONNECT.
2023-05-16 15:35:07.00000EMAIL RECIEVED BY PERMITTING MERAKI
 