-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 23030906
Plan Review Stops For Permit 23030906
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status   Date 10-03-2023 Cont ID  
Sent By elthomps Date 10-03-2023 Time 09:13 Rev Time 0.00
Received By elthomps Date 08-11-2023 Time 15:30 Sent To  
Notes
2023-10-03 09:14:41.00000SAME PLANS WERE SUBMITTED- COMPANY REVCIEVED THE LAST
 REVIEW TO A WRONG EMAIL.
  
2023-08-11 15:30:54.00000SENT IN REVISED PLANS 8/11 BY EXPERT SOLAR
 

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 07-27-2023 Cont ID  
Sent By cdorman Date 07-27-2023 Time 17:07 Rev Time 0.00
Received By cdorman Date 07-14-2023 Time 11:35 Sent To  
Notes
2023-07-28 08:04:06.00000SENT REVISED PLANS 07/28/23
2023-07-14 11:36:05.00000EMAILED IN BY EXPERT SOLAR
 

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 07-13-2023 Cont ID  
Sent By cdorman Date 07-13-2023 Time 15:23 Rev Time 0.00
Received By cdorman Date 07-13-2023 Time 10:36 Sent To  
Notes
2023-07-13 15:22:56.00000REVISION, SHHET E01: SHOW OVERCURRENT PROTECTION IN PV
 DISCONNECT AS 60 AMPS (34 X 1.21 X 1.25 = 51.43) 50A
 FUSES ARE UNDERSIZED FOR 125% OF COMBINED INVERTER
 OUTPUT.
2023-07-13 10:37:06.00000EXPERT SOLAR

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 04-05-2023 Cont ID  
Sent By cdorman Date 04-05-2023 Time 16:06 Rev Time 0.00
Received By cdorman Date 03-21-2023 Time 12:22 Sent To  
Notes
2023-03-21 12:22:48.00000PERMITTING@EXPERTSOLARFL.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved