-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 23020109
Plan Review Stops For Permit 23020109
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 04-05-2023 Cont ID  
Sent By cdorman Date 04-05-2023 Time 16:09 Rev Time 0.00
Received By cdorman Date 03-21-2023 Time 12:15 Sent To  
Notes
2023-03-21 12:16:15.00000ORLANDOPERMITS@LGCYPOWER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-27-2023 Cont ID  
Sent By cdorman Date 02-27-2023 Time 07:59 Rev Time 0.00
Received By cdorman Date 02-13-2023 Time 07:59 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 02-03-2023 Cont ID  
Sent By cdorman Date 02-03-2023 Time 15:31 Rev Time 0.00
Received By cdorman Date 02-03-2023 Time 09:01 Sent To  
Notes
2023-02-03 15:31:13.00000VIOLATION OF 2017 NEC 705.12 (B)(2)(3)(B).
 125% OF THE COMBINED INVERTER OUTPUTS PLUS THE RATING
 OF THE MAIN BREAKER EXCEEDS 120% OF THE BUS RATING.
 [(21 X 1.21) X 1.25] + 150 = 181.76.
 150 X 1.2 = 180.
  
2023-02-03 09:01:38.00000ORLANDOPERMITS@LGCYPOWER.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved