Plan Review Details - Permit 22110073
Plan Review Stops For Permit 22110073
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status C Date 12-15-2022 Cont ID  
Sent By cdorman Date 12-15-2022 Time 13:04 Rev Time 0.00
Received By cdorman Date 12-14-2022 Time 08:08 Sent To  
Notes
2022-12-15 13:04:09.00000CONDITIONAL APPROVAL PER APPLICATION OF EXAMINER'S NOTE
 ON SHEET E-1: CONDUCTORS BETWEEN SMART SWITCH AND
 BACK-UP PANEL MUST BE MIN #1 CU (125A OVERCURRENT
 PROTECTION). THESE CONDUCTORS ARE NOT SUBJECT TO
 DERATING PER 310.15 (B)(7).
2022-12-14 08:09:11.00000REVISION DROPPED OFF

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-03-2022 Cont ID  
Sent By cdorman Date 11-03-2022 Time 16:25 Rev Time 0.00
Received By cdorman Date 11-01-2022 Time 14:29 Sent To  
Notes
2022-11-03 16:25:26.00000SHEET E-1:
 1] CONDUCTORS BETWEEN PV DISCONNECT AND SMART SWITCH
 (FUSED AT 60A) MUST BE MINIMUM #6 CU.
 2] CONDUCTORS FOR SUPPLY-SIDE TAP AND BETWEEN SMART
 SWITCH AND BACKUP PANEL (FUSED AT 125A) MUST BE MINIMUM
 #1 CU. THESE CONDUCTORS DO NOT SUPPLY THE ENTIRE
 DWELLING UNIT AND ARE NOT SUBJECT TO DERATING PER
 310.15 (B)(7).