Plan Review Details - Permit 22100358
Plan Review Stops For Permit 22100358
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 6 Status A Date 05-03-2023 Cont ID  
Sent By cdorman Date 05-03-2023 Time 16:20 Rev Time 0.00
Received By cdorman Date 04-25-2023 Time 11:03 Sent To  
Notes
2023-04-25 11:03:49.00000REVISION PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status D Date 04-12-2023 Cont ID  
Sent By cdorman Date 04-12-2023 Time 16:04 Rev Time 0.00
Received By cdorman Date 04-10-2023 Time 15:19 Sent To  
Notes
2023-04-12 16:04:00.00000SHEET E01: CONDUCTORS BETWEEN MAIN SERVICE PANEL AND
 GATEWAY ARE UNDERSIZED FOR 200A OVERCURRENT PROTECTION.
 INCREASE CONDUCTOR SIZE TO 3/0 COPPER, OR REDUCE
 OVERCURRENT PROTECTION TO 150A TO USE INDICATED 1/0
 COPPER CONDUCTORS.
2023-04-10 15:20:23.00000REVISION FROM INTERCONNECTION@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status D Date 03-21-2023 Cont ID  
Sent By cdorman Date 03-21-2023 Time 16:11 Rev Time 0.00
Received By cdorman Date 03-17-2023 Time 16:10 Sent To  
Notes
2023-03-21 16:11:45.00000RECEIVED REVISED PLANS WITHOUT NOTED CORRECTIONS TO
 SHEET E-01.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 03-08-2023 Cont ID  
Sent By cdorman Date 03-08-2023 Time 16:02 Rev Time 0.00
Received By cdorman Date 03-07-2023 Time 14:18 Sent To  
Notes
2023-03-08 16:02:43.00000SHEET E01: 200A RATED CONDUCTORS BETWEEN EXISTING
 EXTERIOR 200A PANEL AND PROPOSED GATEWAY ARE SHOWN
 TERMINATED INTO A 30A CIRCUIT BREAKER IN THE EXTERIOR
 PANEL.
 1] CORRECT THE OVERCURRENT PROTECTION AND TERMINATION
 METHOD FOR THESE CONDUCTORS
 2] ADD AN EQUIPMENT GROUNDING CONDUCTOR WITH THIS SET
 OF CONDUCTORS (SIZED PER TABLE 250.122)
2023-03-07 14:19:07.00000PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 12-09-2022 Cont ID  
Sent By cshackel Date 12-09-2022 Time 08:52 Rev Time 0.00
Received By cshackel Date 11-03-2022 Time 13:42 Sent To  
Notes
2022-12-09 08:52:43.00000NEEDS PERMIT FOR PERGOLA THAT THE SOLAR IS GOING ON????
2022-11-03 13:42:20.00000REVISED PLANS DROPPED OFF PER CHUCKS REQUEST

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By slozada Date 10-11-2022 Time 08:15 Sent To  
Notes
2022-11-03 08:42:10.00000PV PLANS APPROVED; NEED APPROVED PLANS AND GENERAL
 CONTRACTOR FOR PERGOLA PRIOR TO ISSUING PERMIT SOLAR
 PERMIT
2022-10-11 08:16:04.00000DROPPED OFF