Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-06-2022 Cont ID  
Sent By cdorman Date 10-06-2022 Time 14:47 Rev Time 0.00
Received By cdorman Date 10-06-2022 Time 08:01 Sent To  
Notes
2022-10-06 14:47:38.00000SHEET E-01, CONDUCTORS BETWEEN COMBINER PANEL AND PV
 DISCONNECT: 75 DEGREE AMPACITY OF #10 CONDUCTORS IS
 LESS THAN 125% OF COMBINED INVERTER OUTPUT, TABLE
 310.15 (B) (16). CHANGE CONDUCTORS TO MINIMUM #8.
 (24 X 1.21) X 1.25 = 36.3; #10 AMPACITY @ 75 DEGREES =
 35. AMPACITY OF CONDUCTOR LIMITED TO EQUIPMENT TERMINAL
 TEMPERATURE, 110.14.