Plan Review Stops For Permit 22081500
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 01-11-2023 Cont ID  
Sent By cdorman Date 01-11-2023 Time 14:49 Rev Time 0.00
Received By cdorman Date 01-10-2023 Time 16:54 Sent To  
Notes
2023-01-10 16:55:19.00000REVISION EMAILED IN FROM
 AORTIZ@SOLARINSTALLERSOFFLORIDA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 01-09-2023 Cont ID  
Sent By cdorman Date 01-09-2023 Time 14:52 Rev Time 0.00
Received By cdorman Date 01-09-2023 Time 08:27 Sent To  
Notes
2023-01-09 14:46:14.00000RECEIVED REVISED ONE-LINE DIAGRAM PROPOSING CHANGING
 SERVICE DISCONNECT (MAIN) BREAKER FROM 150A TO 125A.
 PROPOSED CHANGE IS IN RESPONSE TO A DISAPPROVED
 INSPECTION ON 1/5/23 WITH NOTES AS FOLLOWS:
  
 125% OF INVERTER OUTPUT PLUS MAIN BREAKER RATING (150A)
 EXCEEDS 120% OF BUS RATING.
 THIS IS A 150A RATED BUS (SQ D #QO30MW150)
 7.7 KW STRING INVERTER
  
 THIS ALTERATION IS NOT APPROVED BECAUSE THE 125A
 SERVICE DISCONNECT IS UNDERSIZED FOR THE CALCULATED
 LOAD. THE INCLUDED LOAD CALCULATION SHOWS A TOTAL
 DEMAND OF 32489 VA. 32489/240 = 135 AMPS.
 THERE IS AN ERROR IN THE FINAL LINE OF THE INCLUDED
 LOAD CALCULATION: THE FULL AMOUNT (NOT 50%) OF THE
 DEMAND VA SHOULD BE DIVIDED BY THE SERVICE VOLTAGE IN
 ORDER TO DETERMINE MINIMUM SERVICE AMPACITY.
2023-01-09 08:28:37.00000REVISION EMAILED IN 01/06/2023 FROM
 AORTIZ@SOLARINSTALLERSOFFLORIDA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 12-27-2022 Cont ID  
Sent By cdorman Date 12-27-2022 Time 08:29 Rev Time 0.00
Received By cdorman Date 11-27-2022 Time 10:38 Sent To  
Notes
2022-12-27 12:36:27.00000EMAIL IS AORTIZ@SOLARINSTALLERSOFFLORIDA.COM WITH AN S
2022-11-27 10:39:33.00000REVISION EMAILED IN AORTIZ@SOLARINSTALLEROFFLORIDA.COM
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 09-08-2022 Cont ID  
Sent By cdorman Date 09-08-2022 Time 15:19 Rev Time 0.00
Received By cdorman Date 08-24-2022 Time 14:10 Sent To  
Notes
2022-08-24 14:10:57.00000AORTIZ@SOLARINSTALLERSOFFLORIDA.COM