Plan Review Details - Permit 22080604
Plan Review Stops For Permit 22080604
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 10-03-2022 Cont ID  
Sent By cdorman Date 10-03-2022 Time 11:41 Rev Time 0.00
Received By cdorman Date 09-13-2022 Time 09:38 Sent To  
Notes
2022-09-13 09:38:29.00000REVISED PLANS PERMITTING@MERAKISOLUTIONS.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-11-2022 Cont ID  
Sent By cdorman Date 08-11-2022 Time 13:45 Rev Time 0.00
Received By cdorman Date 08-10-2022 Time 16:07 Sent To  
Notes
2022-08-11 13:45:24.00000SHEET PV-05: CONDUCTORS BETWEEN NEW COMBINER PANEL AND
 NEW PV DISCONNECT ARE NOT IDENTIFIED; CONDUCTOR ID #5
 IS UNDERSIZED FOR 80A OCPD.
 SHEET PV-07: AC LABEL MUST SHOW COMBINED MAXIMUM
 INVERTER OUTPUT (BOTH EXISTING AND PROPOSED SYSTEM AS A
 TOTAL)
2022-08-10 16:08:06.00000PERMITTING@MERAKISOLTUIONS.COM