Plan Review Details - Permit 22071374
Plan Review Stops For Permit 22071374
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status A Date 12-12-2022 Cont ID  
Sent By cdorman Date 12-12-2022 Time 14:49 Rev Time 0.00
Received By cdorman Date 12-12-2022 Time 14:49 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status R Date 11-21-2022 Cont ID  
Sent By cdorman Date 11-21-2022 Time 13:40 Rev Time 0.00
Received By cdorman Date 11-21-2022 Time 13:33 Sent To  
Notes
2022-11-21 13:40:18.00000PLANS ARE COMPLETE, BUT A CLARIFICATION/REVISION IS
 REQUIRED ON THE ONE-LINE ELECTRICAL DIAGRAM:
 SHOW OVERCURRENT PROTECTION USED FOR #6 CONDUCTORS
 BETWEEN GENERATOR AND MDP. THE 100A BACKFED BREAKER
 PROPOSED FOR THE MDP IS OVERSIZED FOR #6. CHANGE
 CONDUCTOR TO MIN #3 CU OR CHANGE BACKFED BREAKER TO 60
 AMP.
 NOTE THAT THE SPECIFICATIONS FOR THE GENERATOR INDICATE
 20KW. AFTER A REVIEW OF THE MANUFACTURER'S WEBSITE, IT
 IS UNCLEAR IF THIS IS MAXIMUM DC INPUT OR MAXIMUM AC
 OUTPUT. IT IS ALSO UNCLEAR IF THERE IS ANY BUILT-IN AC
 OUTPUT OVERCURRENT PROTECTION ON THE GENERATOR; IF SO,
 THIS WILL DETERMINE THE OUTPUT CONDUCTOR SIZE AND THE
 BACKFED BREAKER SIZE.
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 09-23-2022 Cont ID  
Sent By cdorman Date 09-23-2022 Time 13:38 Rev Time 0.00
Received By cdorman Date 09-23-2022 Time 13:31 Sent To  
Notes
2022-09-23 13:38:11.000001] 20 KW INVERTER OUTPUT REQUIRES MIN 110A OVERCURRENT
 DEVICE SUPPLIED BY MINIMUM #2 COPPER. PV CIRCUITS ARE
 CONSIDERED CONTINUOUS PER 690.8 (B). (20000/240) X 1.25
 = 104 AMPS. REQUIREMENT CAN BE WAIVED IF MANUFACTURER
 DOCUMENTATION SHOWS THE SYSTEM TESTED AND LISTED TO BE
 USED IN CONJUNCTION WITH 100 AMP OVERCURRENT
 PROTECTION.
 2] STILL NEED SPECIFICATION SHEET FOR INTERLOCK KIT.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 09-13-2022 Cont ID  
Sent By cdorman Date 09-13-2022 Time 14:23 Rev Time 0.00
Received By cdorman Date 09-12-2022 Time   Sent To  
Notes
2022-09-13 14:23:14.000001] CHANGE BACKFED CIRCUIT BREAKER TO 60 AMPS
 2] PROVIDE SPECIFICATION SHEET FOR INTENDED INTERLOCK
 KIT
 SEND ALL DOCUMENTS IN PDF FORMAT ONLY

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-26-2022 Cont ID  
Sent By cdorman Date 07-26-2022 Time 14:19 Rev Time 0.00
Received By cdorman Date 07-26-2022 Time 08:36 Sent To  
Notes
2022-07-26 14:19:12.000001] PROVIDE ROOF PLAN VIEW SHOWING PLACEMENT OF MODULES
 IN RELATION TO EACH EAVE, RIDGE, HIP, OR VALLEY.
 INDICATE THESE DIMENSIONS ON PLAN; MAINTAIN COMPLIANCE
 WITH FLORIDA FIRE PREVENTION CODE 11.12.2.2.2 PROVIDING
 FOR FIRE ACCESS PATHS.
 2] PROVIDE ADDITIONAL SPECIFICATION SHEET(S) FOR POWERX
 GENERATOR, INCLUDING MANUFACTURER GUIDELINES FOR
 INSTALLATION. SPECIFICATION SHEETS SHOULD INCLUDE
 ENOUGH DETAIL TO DETERMINE ONBOARD OVERCURRENT
 PROTECTION AND DISCONNECTING MEANS, AND SHOULD SHOW
 TYPICAL CONNECTION DIAGRAMS FOR FIELD-INSTALLED WIRING.
 3] PROVIDE ONE-LINE ELECTRICAL DIAGRAM SHOWING ALL
 FIELD-INSTALLED WIRING. DIAGRAM MUST INDICATE CONDUCTOR
 AND RACEWAY TYPES AND SIZES, ALONG WITH TERMINATIONS TO
 ALL MAJOR COMPONENTS.
2022-07-26 08:36:47.00000EMAILED IN FORM OWNER, R.PETROVICH@ICLOUD.COM
 NEEDS VALUATION OF JOB