Plan Review Stops For Permit 22070386
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 08-04-2022 Cont ID  
Sent By cdorman Date 08-04-2022 Time 15:12 Rev Time 0.00
Received By cdorman Date 07-18-2022 Time 16:26 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 07-11-2022 Cont ID  
Sent By cdorman Date 07-11-2022 Time 15:12 Rev Time 0.00
Received By cdorman Date 07-08-2022 Time 11:12 Sent To  
Notes
2022-07-11 15:12:31.00000125% OF INVERTER OUTPUT PLUS RATING OF MAIN BREAKER
 EXCEEDS 120% OF BUS RATING. SEE 705.12 (B) (2).
2022-07-08 11:12:41.00000PERMITS@SUNVENA.COM